Emergency Lighting Control Unit for KO Mounting
ELCU-200
Wattstopper
Bazaarvoice SAP Hybris Integration Version 2.8.1
Wattstopper’s ELCU-200 Emergency Lighting Control Unit is a self-contained device that allows any standard lighting control device to control emergency lighting in conjunction with normal lighting in any area within a building.
Voltage
120/277 VAC
- 120/277 VAC
- 347 VAC
- Send
- Save as PDF
-
Added to Favorites Go to favoritesRemove from favorites?Something went wrong. Please try again later.
Features
- Eliminates energy waste caused by emergency lighting that is always on
- Integral push-to-test button activates emergency mode for a true test condition
- Connects to EMTS-100 Remote Test Switch or other input to activate emergency on from a remote location
- Operates as a control device or as a shunt
- Senses local single circuit power failure
- Zero cross switching technology for reliability and increased product life
- Compatible with Wattstopper occupancy sensors, daylighting controls, lighting control panels, and dimmers
Specifications
General Info
Color | Red, White | ||
Product Series | ELCU | ||
Type | Emergency Load Controller | ||
Application Sector | Commercial | ||
Product Line | Wattstopper | ||
Country Of Origin | China | ||
Features | Push-to-Test on Device | ||
Installation Location | Above Ceiling | ||
Warranty Type | 5-Year | ||
Standard | UL 924, NEC, OSHA, NFPA 101, UL 2043 | ||
UPC Number | 754182923052 |
Dimensions
Product Depth US | 1.9 in | ||
Product Height US | 3.0 in | ||
Product Volume US | 26.1 cu in | ||
Product Width US | 2.2 in | ||
Product Weight US | 0.3 lb |
Additional Information
RoHS Compliant | Yes | This product meets the material restrictions of Article 4 of the RoHS Directive (2011/65/EU), including Commission Delegated Directive 2015/863. |
Technical Information
Wire Connection Type | Flying Leads | ||
Compatibility | EMTS-100 | ||
Contact Configuration | N-C | ||
Contact Rating | 24 VDC | ||
Indoor/Outdoor | Indoor | ||
Input Voltage | 120 to 277 VAC | ||
Line Frequency | 50 Hz, 60 Hz | ||
Load Rating | 10 A @ 120 VAC, 20 A @ 277 VAC | ||
Mounting Type | 1/2 in Knockout | ||
Number of Relays | 0 | ||
Operating Temperature | 32°-131°F | ||
Operating Temperature Max | 131 F | ||
Operating Temperature Min | 32 F | ||
Operating Humidity | 5-95% RH (Non-Condensing) | ||
Storage Temperature | 23° - 176° F |